BAF: Building Automation Functions.

Release 2022-05-29

Latest version:
https://w3id.org/baf#
Revision:
v1.0.0
Issued on:
2022-05-29
Authors:
https://orcid.org/0000-0001-7604-8543
https://www.linkedin.com/in/hervepruvost
Hervé Pruvost
Publisher:
Fraunhofer IIS/EAS
Imported Ontologies:
CTRLont
ESIM
Download serialization:
JSON-LD RDF/XML N-Triples TTL
License:
http://creativecommons.org/licenses/by-sa/4.0
Visualization:
Visualize with WebVowl
Cite as:
Pruvost. H. (2023): The BAF ontology - a formalization of generic building automation functions for heating, ventilation and air conditioning systems. https://w3id.org/baf.

Ontology Specification Draft

Abstract

The BAF (Building Automation Functions) model is a catalogue of generic control functions usually implemented by automation engineers.

Introduction back to ToC

This is a place holder text for the introduction. The introduction should briefly describe the ontology, its motivation, state of the art and goals.

Namespace declarations

Table 1: Namespaces used in the document
baf<https://w3id.org/baf#>
owl<http://www.w3.org/2002/07/owl>
rdf<http://www.w3.org/1999/02/22-rdf-syntax-ns>
xml<http://www.w3.org/XML/1998/namespace>
xsd<http://www.w3.org/2001/XMLSchema>
dcterms<http://purl.org/dc/terms>
rdfs<http://www.w3.org/2000/01/rdf-schema>
CTRLont<https://w3id.org/ibp/CTRLont>
vann<http://purl.org/vocab/vann>
esim<http://org.fhg.iis.eas.eee.esim/ESIMonto>

BAF: Overview back to ToC

This ontology has the following classes and properties.

Classes

Annotation Properties

Named Individuals

BAF: Description back to ToC

This is a placeholder text for the description of your ontology. The description should include an explanation and a diagram explaining how the classes are related, examples of usage, etc.

Cross-reference for BAF classes, object properties and data properties back to ToC

This section provides details for each class and property defined by BAF.

Classes

1st order low pass filterc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbFirstOrderLowPassFilter

has super-classes
Analog signal c
has members
1st Order Low-Pass Filter Pattern ni

1st order low pass filter for AI 0-32767c back to ToC or Class ToC

IRI: https://w3id.org/baf#FbFirstOrderLowPassFilterForAI0-32767

has super-classes
Analog signal c

1st order low pass filter for bus signalsc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbFirstOrderLowPassFilterForBusSignals

has super-classes
Analog signal c

1st order low pass filter for temperaturesc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbFirstOrderLowPassFilterForTemperatures

has super-classes
Analog signal c

Actuationof continuous dampersc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbActuationofContinuousDampers

has super-classes
Damper control c
has members
Actuation of Continuous Dampers Pattern ni

Actuationof2-Point dampersc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbActuationof2PointDampers

has super-classes
Damper control c

Air-Side antifreeze protectionc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbAirSideAntifreezeProtection

has super-classes
Antifreeze protection c

Analog 3-Point signalc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbAnalog3PointSignal

has super-classes
General driver c
has members
Analog 3-Point Signal Pattern ni

Anti legionnaires disease functionc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbAntiLegionnairesDiseaseFunction

has super-classes
Set value adjustment c

Antifreeze protectionc back to ToC or Class ToC

IRI: https://w3id.org/baf#AntifreezeProtection

has super-classes
h v a c function c
has sub-classes
Air-Side antifreeze protection c, Water-Side antifreeze protection c

Averaged outside temperaturec back to ToC or Class ToC

IRI: https://w3id.org/baf#FbAveragedOutsideTemperature

has super-classes
Temperature evaluation c

Blinkerc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbBlinker

has super-classes
Miscellaneous function c

Blocking protection for continuous driversc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbBlockingProtectionForContinuousDrivers

has super-classes
Miscellaneous function c

Boiler controlc back to ToC or Class ToC

IRI: https://w3id.org/baf#BoilerControl

has super-classes
h v a c function c
has sub-classes
Boiler module for 2-Level boiler c, Boiler module for modulating boiler c, Boiler strategy for two boilers c

Boiler module for 2-Level boilerc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbBoilerModuleFor2LevelBoiler

has super-classes
Boiler control c
has members
Boiler Module for 2-Level Boiler Pattern ni

Boiler module for modulating boilerc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbBoilerModuleForModulatingBoiler

has super-classes
Boiler control c

Boiler strategy for two boilersc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbBoilerStrategyForTwoBoilers

has super-classes
Boiler control c

Calculationof supply temperaturec back to ToC or Class ToC

IRI: https://w3id.org/baf#FbCalculationofSupplyTemperature

has super-classes
Set value adjustment c

Cascade controllerc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbCascadeController

has super-classes
Controller c
has members
Cascade Controller Pattern ni

Characteristic curvec back to ToC or Class ToC

IRI: https://w3id.org/baf#CharacteristicCurve

has super-classes
h v a c function c
has sub-classes
Four-point characteristic curve c, KTY Characteristic curve c, Two-point characteristic c

Collective malfunctionc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbCollectiveMalfunction

has super-classes
System monitoring c

Comfort zone controllerc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbComfortZoneController

has super-classes
Miscellaneous function c

Control of 2-Point driversc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbControlOf2PointDrivers

has super-classes
General driver c

Control of continuous driversc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbControlOfContinuousDrivers

has super-classes
General driver c

Controllerc back to ToC or Class ToC

IRI: https://w3id.org/baf#Controller

has super-classes
h v a c function c
has sub-classes
Cascade controller c, PIDController c, PIDControllerwith two setsof control parameters c, PILimit controller c, Sequence controller c, Two-Point controllerfor DHWPreparation c

Cooling sequencec back to ToC or Class ToC

IRI: https://w3id.org/baf#FbCoolingSequence

has super-classes
Sequence c

Damped temperaturec back to ToC or Class ToC

IRI: https://w3id.org/baf#FbDampedTemperature

has super-classes
Temperature evaluation c

Damper controlc back to ToC or Class ToC

IRI: https://w3id.org/baf#DamperControl

has super-classes
h v a c function c
has sub-classes
Actuationof continuous dampers c, Actuationof2-Point dampers c

Dehumidifying sequencec back to ToC or Class ToC

IRI: https://w3id.org/baf#FbDehumidifyingSequence

has super-classes
Sequence c

Energy recovery sequencec back to ToC or Class ToC

IRI: https://w3id.org/baf#FbEnergyRecoverySequence

has super-classes
Sequence c
has members
Energy Recovery Sequence Pattern ni

Enthalpyc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbEnthalpy

has super-classes
Temperature evaluation c

Fan controlc back to ToC or Class ToC

IRI: https://w3id.org/baf#FanControl

has super-classes
h v a c function c
has sub-classes
Fan1-Level c, Fan2-Level c, Fan3-Level c, Fanwith frequency converter c

Fan1-Levelc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbFan1Level

has super-classes
Fan control c

Fan2-Levelc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbFan2Level

has super-classes
Fan control c

Fan3-Levelc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbFan3Level

has super-classes
Fan control c

Fanwith frequency converterc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbFanwithFrequencyConverter

has super-classes
Fan control c

Filter monitoringc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbFilterMonitoring

has super-classes
System monitoring c

Four-point characteristic curvec back to ToC or Class ToC

IRI: https://w3id.org/baf#FuFourPointCharacteristicCurve

has super-classes
Characteristic curve c
has members
Four-Point Characteristic Curve Pattern ni

General driverc back to ToC or Class ToC

IRI: https://w3id.org/baf#GeneralDriver

has super-classes
h v a c function c
has sub-classes
Analog 3-Point signal c, Control of 2-Point drivers c, Control of continuous drivers c, PWM Output c

Global collective malfunctionc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbGlobalCollectiveMalfunction

has super-classes
System monitoring c

Heat exchanger controlc back to ToC or Class ToC

IRI: https://w3id.org/baf#HeatExchangerControl

has super-classes
h v a c function c
has sub-classes
Plate-Type heat exchanger c, Rotary heat exchanger c, Run-around coil c

Heating characteristicsc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbHeatingCharacteristics

has super-classes
Set value adjustment c

Heating sequencec back to ToC or Class ToC

IRI: https://w3id.org/baf#FbHeatingSequence

has super-classes
Sequence c
has members
Heating Sequence Pattern ni

Humidifierc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbHumidifier

has super-classes
Pump control c, Valve control c

Humidifying sequencec back to ToC or Class ToC

IRI: https://w3id.org/baf#FbHumidifyingSequence

has super-classes
Sequence c

Hysteresisc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbHysteresis

has super-classes
Miscellaneous function c

Impulse counterc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbImpulseCounter

has super-classes
Miscellaneous function c

KTY Characteristic curvec back to ToC or Class ToC

IRI: https://w3id.org/baf#FuKTYCharacteristicCurve

has super-classes
Characteristic curve c

Min. Value, Avg. Value and Max. Valuec back to ToC or Class ToC

IRI: https://w3id.org/baf#FbMinValueAvgValueAndMaxValue

has super-classes
Miscellaneous function c

Miscellaneous functionc back to ToC or Class ToC

IRI: https://w3id.org/baf#MiscellaneousFunction

has super-classes
h v a c function c
has sub-classes
Blinker c, Blocking protection for continuous drivers c, Comfort zone controller c, Hysteresis c, Impulse counter c, Min. Value, Avg. Value and Max. Value c, Operating hours counter c, Ramp c, Statusanzeige als STRING c, Unit monitoring c

Mixed air sequencec back to ToC or Class ToC

IRI: https://w3id.org/baf#FbMixedAirSequence

has super-classes
Sequence c
has members
Mixed Air Sequence Pattern ni

Operating hours counterc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbOperatingHoursCounter

has super-classes
Miscellaneous function c

Optimized supply temperaturec back to ToC or Class ToC

IRI: https://w3id.org/baf#FbOptimizedSupplyTemperature

has super-classes
Set value adjustment c

Overheatingand condensation protectionc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbOverheatingandCondensationProtection

has super-classes
Set value adjustment c

PIDControllerc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbPIDController

has super-classes
Controller c

PIDControllerwith two setsof control parametersc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbPIDControllerwithTwoSetsofControlParameters

has super-classes
Controller c

PIDSingle room controllerc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbPIDSingleRoomController

has super-classes
Single room control c

PILimit controllerc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbPILimitController

has super-classes
Controller c

Plate-Type heat exchangerc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbPlateTypeHeatExchanger

has super-classes
Heat exchanger control c
has members
Plate-Type Heat Exchanger Pattern ni

Point individual room controllerc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbTwoPointIndividualRoomController

has super-classes
Single room control c

Pumpc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbPump

has super-classes
Pump control c

Pump controlc back to ToC or Class ToC

IRI: https://w3id.org/baf#PumpControl

has super-classes
h v a c function c
has sub-classes
Humidifier c, Pump c, Pumpwith frequency converter c, Ventil und Pumpe c

Pumpwith frequency converterc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbPumpwithFrequencyConverter

has super-classes
Pump control c

PWM Outputc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbPWMOutput

has super-classes
General driver c

Rampc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbRamp

has super-classes
Miscellaneous function c

Reduced minimum fresh airc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbReducedMinimumFreshAir

has super-classes
Set value adjustment c

Rotary heat exchangerc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbRotaryHeatExchanger

has super-classes
Heat exchanger control c

Run-around coilc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbRunAroundCoil

has super-classes
Heat exchanger control c

Scaling of output values 0 to 32767c back to ToC or Class ToC

IRI: https://w3id.org/baf#FuScalingOfOutputValues0to32767

has super-classes
Analog signal c

Scaling of temperature valuesin °Cc back to ToC or Class ToC

IRI: https://w3id.org/baf#FuScalingOfTemperatureValuesInDeg

has super-classes
Analog signal c

Scalingof input values0to32767c back to ToC or Class ToC

IRI: https://w3id.org/baf#FuScalingofInputValues0to32767

has super-classes
Analog signal c

Sequencec back to ToC or Class ToC

IRI: https://w3id.org/baf#Sequence

has super-classes
h v a c function c
has sub-classes
Cooling sequence c, Dehumidifying sequence c, Energy recovery sequence c, Heating sequence c, Humidifying sequence c, Mixed air sequence c

Sequence controllerc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbSequenceController

has super-classes
Controller c
has members
Sequence Controller Pattern ni

Single room controlc back to ToC or Class ToC

IRI: https://w3id.org/baf#SingleRoomControl

has super-classes
h v a c function c
has sub-classes
PIDSingle room controller c, Point individual room controller c

Start stop heating circuit controlc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbStartStopHeatingCircuitControl

has super-classes
System monitoring c

Start/Stopc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbStartStop

has super-classes
System monitoring c

Start/Stop optimizationc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbStartStopOptimization

has super-classes
System monitoring c

Statusanzeige als STRINGc back to ToC or Class ToC

IRI: https://w3id.org/baf#FuStatusIndicationAsString

has super-classes
Miscellaneous function c

Summer compensationc back to ToC or Class ToC

IRI: https://w3id.org/baf#FuSummerCompensation

has super-classes
Set value adjustment c

Summer night ventilationc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbSummerNightVentilation

has super-classes
System monitoring c

System monitoringc back to ToC or Class ToC

IRI: https://w3id.org/baf#SystemMonitoring

has super-classes
h v a c function c
has sub-classes
Collective malfunction c, Filter monitoring c, Global collective malfunction c, Start stop heating circuit control c, Start/Stop c, Start/Stop optimization c, Summer night ventilation c

Temperature evaluationc back to ToC or Class ToC

IRI: https://w3id.org/baf#TemperatureEvaluation

has super-classes
h v a c function c
has sub-classes
Averaged outside temperature c, Damped temperature c, Enthalpy c

Two-point characteristicc back to ToC or Class ToC

IRI: https://w3id.org/baf#FuTwoPointCharacteristic

has super-classes
Characteristic curve c

Two-Point controllerfor DHWPreparationc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbTwoPointControllerforDHWPreparation

has super-classes
Controller c

typConfigAnalog3Point_01c back to ToC or Class ToC

IRI: https://w3id.org/baf#typConfigAnalog3Point_01

has super-classes
parameter
has members
.rHysteresis ni, .tMaxRunTime ni, .tOverride ni, .xLimitSwitch ni

typConfigCascadeControllerc back to ToC or Class ToC

IRI: https://w3id.org/baf#typConfigCascadeController

has super-classes
parameter
has members
.rDeadZone ni, .rKp ni, .rOffsetMaxReferenceValue ni, .rOffsetMinReferenceValue ni, .rTn ni, .tDelaySwitchOver ni, .xControlSpeedLevel ni

typConfigContinuousDamperc back to ToC or Class ToC

IRI: https://w3id.org/baf#typConfigContinuousDamper

has super-classes
parameter
has members
.rMinDeviationMovement ni, .rTolerance ni, .rY_Min ni, .tOnDelayAlarm ni, .xFeedbackDamper ni

typConfigLowPassFilterc back to ToC or Class ToC

IRI: https://w3id.org/baf#typConfigLowPassFilter

has super-classes
parameter
has members
.rDefaultValue ni, .rHighLimitAlarm ni, .rLowLimitAlarm ni, .rOffset ni, .tAlarm ni, .tCycleTime ni, .tT1 ni, .xAutoQuit ni

typConfigSequencec back to ToC or Class ToC

IRI: https://w3id.org/baf#typConfigSequence

has super-classes
parameter
has members
.bSequenceNumber ni, .rX1 ni, .rX2 ni

typConfigSequenceControllerc back to ToC or Class ToC

IRI: https://w3id.org/baf#typConfigSequenceController

has super-classes
parameter
has members
.bMaxSequenceNumber ni, .rDeadZone ni, .rDeviation ni, .rKp1 ni, .rKp2 ni, .rTd1 ni, .rTd2 ni, .rTn1 ni, .rTn2 ni

typConfigValveAndPumpc back to ToC or Class ToC

IRI: https://w3id.org/baf#typConfigValveAndPump

has super-classes
parameter
has members
.rMinOutsideTemperature ni, .rValveChimneySweep ni, .rY_Min ni, .tMaxChimneySweepFunction ni, .tMaxOff ni, .tOffDelay ni, .tSwitchOn ni, .xAutoQuit ni, .xBlockingProtection ni, .xPumpWinter ni, .xThreeWayValve ni

Unit monitoringc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbUnitMonitoring

has super-classes
Miscellaneous function c

Valve controlc back to ToC or Class ToC

IRI: https://w3id.org/baf#ValveControl

has super-classes
h v a c function c
has sub-classes
Humidifier c, Ventil und Pumpe c

Ventil und Pumpec back to ToC or Class ToC

IRI: https://w3id.org/baf#FbValveandPump

has super-classes
Pump control c, Valve control c
has members
Valve and Pump Pattern ni

Volume flow regulatorc back to ToC or Class ToC

IRI: https://w3id.org/baf#VolumeFlowRegulator

has super-classes
h v a c function c

Water-Side antifreeze protectionc back to ToC or Class ToC

IRI: https://w3id.org/baf#FbWaterSideAntifreezeProtection

has super-classes
Antifreeze protection c

Annotation Properties

bibliographic citationap back to ToC or Annotation Property ToC

IRI: http://purl.org/dc/terms/bibliographicCitation

Named Individuals

Boiler Module for 2-Level Boiler Patternni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#Fb2LevelBoilerPattern

Pattern of function block for Boiler Module for 2-Level Boiler (Fb2LevelBoiler)
belongs to
Enumerated control function pattern c
Boiler module for 2-Level boiler c

.bMaxSequenceNumberni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_bMaxSequenceNumber

Max. number of sequences used Value range = 2 – 4 Default setting = 2
belongs to
typConfigSequenceController c

.bSequenceNumberni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_bSequenceNumber

Sequence number (from cooling toward heating) Value range = 1 – 4
belongs to
typConfigSequence c

.rDeadZoneni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rDeadZone

Dead zone +/- [K] Default setting = 0
belongs to
typConfigCascadeController c
typConfigSequenceController c

.rDefaultValueni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rDefaultValue

Defined output value as long as the xAlarm output is set Default setting = 0
belongs to
typConfigLowPassFilter c

.rDeviationni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rDeviation

Maximum deviation between specified/actual values for the second set of controller parameters [%] Default setting = 0 (no switchover)
belongs to
typConfigSequenceController c

.rDiffBoilerAndReturnTemperatureni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rDiffBoilerAndReturnTemperature

Max. temperature difference between boiler and return temperature for deactivation of the boiler circuit pump [K]. Default setting = 5
belongs to
typConfig2LevelBoiler c

.rHighLimitAlarmni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rHighLimitAlarm

Upper limit for value of the output signal alarm Default setting = 32768
belongs to
typConfigLowPassFilter c

.rHysteresisni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rHysteresis

belongs to
typConfig2LevelBoiler c
typConfigAnalog3Point_01 c

.rKpni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rKp

Proportional gain (P portion) Default setting = 2.5
belongs to
typConfigCascadeController c

.rKp1ni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rKp1

Proportional gain (P portion) for the first set of controller parameters Default setting = 2.5
belongs to
typConfigSequenceController c

.rKp2ni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rKp2

Proportional gain (P portion) for the second set of controller parameters Default setting = 2.5
belongs to
typConfigSequenceController c

.rKpMinReturnTemperatureni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rKpMinReturnTemperature

Proportional gain (P portion). Default setting = 12
belongs to
typConfig2LevelBoiler c

.rLeadHysteresisni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rLeadHysteresis

Hysteresis as the lead boiler for the individual limit values. Default setting = 5
belongs to
typConfig2LevelBoiler c

.rLeadOffsetReferenceTemperatureni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rLeadOffsetReferenceTemperature

Offset to the specified boiler temperature as lead boiler [K]. Default setting = 5
belongs to
typConfig2LevelBoiler c

.rLowLimitAlarmni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rLowLimitAlarm

Lower limit for value of the output signal alarm Default setting = -32767
belongs to
typConfigLowPassFilter c

.rMaxBoilerTemperatureni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rMaxBoilerTemperature

Maximum boiler temperature at Level 1 [°C]. Default setting = 90
belongs to
typConfig2LevelBoiler c

.rMaxBoilerTemperatureLevel2ni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rMaxBoilerTemperatureLevel2

Maximum boiler temperature at Level 2 [°C]. Default setting = 85
belongs to
typConfig2LevelBoiler c

.rMaxReturnTemperatureni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rMaxReturnTemperature

Maximum return temperature [°C]. Default setting = 75
belongs to
typConfig2LevelBoiler c

.rMinBoilerTemperatureni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rMinBoilerTemperature

Minimum boiler temperature [°C]. Default setting = 50
belongs to
typConfig2LevelBoiler c

.rMinDeviationMovementni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rMinDeviationMovement

Minimum deviation for detection of motion [%] Default setting = 5
belongs to
typConfigContinuousDamper c

.rMinOutsideTemperatureni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rMinOutsideTemperature

Minimum outside temperature for freeze protection [°C] Default setting = 2 °C
belongs to
typConfigValveAndPump c

.rMinReturnTemperatureni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rMinReturnTemperature

Minimum return temperature [°C]. Default setting = 50
belongs to
typConfig2LevelBoiler c

.rOffsetni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rOffset

Measured value compensation for the input Default setting = 0
belongs to
typConfigLowPassFilter c

.rOffsetMaxReferenceValueni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rOffsetMaxReferenceValue

Offset for the maximum reference value for the slave controller as a function of the reference value [K] Default setting = 6 K
belongs to
typConfigCascadeController c

.rOffsetMinReferenceValueni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rOffsetMinReference

Offset for the minimum reference value for the slave controller as a function of the reference value [K] Default setting = 4 K
belongs to
typConfigCascadeController c

.rOffsetReferenceTemperatureni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rOffsetReferenceTemperature

Offset to the specified boiler temperature [K]. Default setting = 3
belongs to
typConfig2LevelBoiler c

.rTd1ni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rTd1

Derivative time (D portion) for the first set of controller parameters [s] Default setting = 0 s
belongs to
typConfigSequenceController c

.rTd2ni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rTd2

Derivative time (D portion) for the second set of controller parameters [s] Default setting = 0 s
belongs to
typConfigSequenceController c

.rTnni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rTn

Reset time of the controller [s] Default setting = 300 s
belongs to
typConfigCascadeController c

.rTn1ni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rTn1

Reset time of the controller for the first set of controller parameters [s] Default setting = 300 s
belongs to
typConfigSequenceController c

.rTn2ni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rTn2

Reset time of the controller for the second set of controller parameters [s] Default setting = 300 s
belongs to
typConfigSequenceController c

.rTnMinReturnTemperatureni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rTnMinReturnTemperature

Reset time of the controller [s]. Default setting = 0
belongs to
typConfig2LevelBoiler c

.rToleranceni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rTolerance

Max. deviation, specified/actual position [%] Default setting = 3
belongs to
typConfigContinuousDamper c

.rValveChimneySweepni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rValveChimneySweep

Chimney sweep function valve position [%] Default setting = 25
belongs to
typConfigValveAndPump c

.rX1ni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rX1

Min. setting value for sequence [%]
belongs to
typConfigSequence c

.rX2ni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rX2

Max. setting value for sequence [%]
belongs to
typConfigSequence c

.rY_Minni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_rY_Min

Minimum set value for valve or damper [%] Default setting = 3
belongs to
typConfigContinuousDamper c
typConfigValveAndPump c

.tAlarmni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_tAlarm

Minimum time on limit violation until an alarm is issued. Default setting: t#10s
belongs to
typConfigLowPassFilter c

.tCycleTimeni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_tCycleTime

Cycle time for the PT1 circuit
belongs to
typConfigLowPassFilter c

.tDelaySwitchOverni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_tDelaySwitchOver

Delay time for switching between the two fan levels Default setting = t#5 m
belongs to
typConfigCascadeController c

.tLeadMinRuntimeLevel1ni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_tLeadMinRuntimeLevel1

Minimum runtime for lead boiler at Level 1. Default setting = t#5 m
belongs to
typConfig2LevelBoiler c

.tLeadSwitchOnDelayLevel2ni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_tLeadSwitchOnDelayLevel2

Switch-on delay for lead boiler at Level 2. Default setting = t#15 m
belongs to
typConfig2LevelBoiler c

.tMaxChimneySweepFunctionni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_tMaxChimneySweepFunction

Maximum duration of chimney sweep function. Default setting = t#15 m
belongs to
typConfig2LevelBoiler c
typConfigValveAndPump c

.tMaxFlushPeriodni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_tMaxFlushPeriod

Maximum time for the startup process. Default setting = t#15 m
belongs to
typConfig2LevelBoiler c

.tMaxOffni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_tMaxOff

Maximum turn-off time of the pump when blocking protection is enabled Default setting = t#48h
belongs to
typConfigValveAndPump c

.tMaxRunTimeni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_tMaxRunTime

Max. running time, which the actuator needs for the max. stroke Default setting: t#120s
belongs to
typConfigAnalog3Point_01 c

.tMaxRuntimeValveni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_tMaxRuntimeValve

Maximum runtime for 2-way valve. Default setting: t#30s
belongs to
typConfig2LevelBoiler c

.tMaxStartupMinBoilerTemperatureni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_tMaxStartupMinBoilerTemperature

Maximum time until minimum boiler temperature is achieved during the startup process. Default setting = t#10 m
belongs to
typConfig2LevelBoiler c

.tMinRuntimeLevel1ni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_tMinRuntimeLevel1

Minimum runtime for lag boiler at Level 1. Default setting = t#3 m
belongs to
typConfig2LevelBoiler c

.tOffDelayni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_tOffDelay

Turn-off delay of the pump Default setting = t#15 m
belongs to
typConfigValveAndPump c

.tOffDelayAdmixingPumpni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_tOffDelayAdmixingPump

Switch-off delay for admixing pump. Default setting = t#1 m
belongs to
typConfig2LevelBoiler c

.tOffDelayFullLoadni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_tOffDelayFullLoad

Switch-off delay for full-load operation. Default setting: t#30s
belongs to
typConfig2LevelBoiler c

.tOffDelayPumpni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_tOffDelayPump

Switch-off delay for boiler circuit pump. Default setting = t#10 m
belongs to
typConfig2LevelBoiler c

.tOnDelayAlarmni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_tOnDelayAlarm

ON-delay for alarm Default setting = t#5 m
belongs to
typConfigContinuousDamper c

.tOnDelayPumpni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_tOnDelayPump

Switch-on delay for boiler circuit pump with one 2-way valve. Default setting = t#2 m
belongs to
typConfig2LevelBoiler c

.tOverrideni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_tOverride

Run-on time after reaching end positions
belongs to
typConfigAnalog3Point_01 c

.tPumpValveMaxOFFni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_tPumpValveMaxOFF

Maximum turn-off time of the pump and valve up to activation of blocking protection. Default setting = t#24h
belongs to
typConfig2LevelBoiler c

.tPumpValveONni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_tPumpValveON

Maintenance run time for pump and valve. Default setting: t#30s
belongs to
typConfig2LevelBoiler c

.tSwitchOnni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_tSwitchOn

Turn-on time of the pump when blocking protection is enabled Default setting: t#60s
belongs to
typConfigValveAndPump c

.tSwitchOnDelayLevel2ni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_tSwitchOnDelayLevel2

Switch-on delay for lag boiler at Level 2. Default setting = t#20 m
belongs to
typConfig2LevelBoiler c

.tT1ni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_tT1

Time constant for the PT1 circuit Default setting: t#2s
belongs to
typConfigLowPassFilter c

.xAdmixingPumpni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_xAdmixingPump

Admixing pump present. Default setting = FALSE
belongs to
typConfig2LevelBoiler c

.xAutoQuitni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_xAutoQuit

Automatic acknowledgement of the alarm or fault messages
belongs to
typConfigLowPassFilter c
typConfigValveAndPump c

.xBlockingProtectionni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_xBlockingProtection

Enable blocking protection. Default setting = TRUE
belongs to
typConfig2LevelBoiler c
typConfigValveAndPump c

.xControlSpeedLevelni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_xControlSpeedLevel

Enable for determining the required fan level Default setting = FALSE
belongs to
typConfigCascadeController c

.xFeedbackDamperni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_xFeedbackDamper

Check-back signal Damper position present Default setting = FALSE
belongs to
typConfigContinuousDamper c

.xLimitSwitchni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_xLimitSwitch

Monitoring of the limit switches Default setting = FALSE
belongs to
typConfigAnalog3Point_01 c

.xPumpWinterni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_xPumpWinter

Enable freeze protection
belongs to
typConfigValveAndPump c

.xSmallWaterVolumeni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_xSmallWaterVolume

Low volume of water in boiler. Default setting = FALSE
belongs to
typConfig2LevelBoiler c

.xThreeWayValveni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_xThreeWayValve

3-way valve present in boiler circuit. Default setting = TRUE
belongs to
typConfig2LevelBoiler c
typConfigValveAndPump c

.xTwoWayValveni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_xTwoWayValve

2-way valve (boiler valve) present. Default setting = FALSE
belongs to
typConfig2LevelBoiler c

.xTwoWayValvePermanentOpenni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#_xTwoWayValvePermanentOpen

2-way valve closed in the event of a fault. Default setting = FALSE
belongs to
typConfig2LevelBoiler c

1st Order Low-Pass Filter Patternni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#FbLowPassFilterPattern

Pattern of function block: 1st Order Low-Pass Filter (FbLowPassFilter)
belongs to
Enumerated control function pattern c
1st order low pass filter c

Actuation of Continuous Dampers Patternni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#FbContinuousDamperPattern

Pattern of function block for Actuation of Continuous Dampers (FbContinuousDamper)
belongs to
Enumerated control function pattern c
Actuationof continuous dampers c

Analog 3-Point Signal Patternni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#FbAnalog3PointPattern

Pattern of function block for Analog 3-Point Signal (FbAnalog3Point)
belongs to
Enumerated control function pattern c
Analog 3-Point signal c

bBoilerNumberni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#bBoilerNumber

Boiler number. Value range = 1 – 2. Default setting = 1
belongs to
input

bLeadBoilerni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#bLeadBoiler

Defining of lead boiler. Value range = 0 – 2 (0 = both boilers in parallel). Default setting = 1
belongs to
input

bManualLevelBoilerni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#bManualLevelBoiler

Boiler level in Manual mode. Value range = 0 – 2
belongs to
input

Cascade Controller Patternni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#FbCascadeControllerPattern

Pattern of function block for Cascade Controller (FbCascadeController)
belongs to
Enumerated control function pattern c
Cascade controller c

dwOperatingMinutesni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#dwOperatingMinutes

Operating time in minutes
belongs to
input
output

Energy Recovery Sequence Patternni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#FbSequenceEnergyRecoveryPattern

Pattern of function block for Energy Recovery Sequence (FbSequenceEnergyRecovery)
belongs to
Enumerated control function pattern c
Energy recovery sequence c

Four-Point Characteristic Curve Patternni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#Fu4Point

Pattern of function block for Four-Point Characteristic Curve (Fu4Point)
belongs to
Enumerated control function pattern c
Four-point characteristic curve c

Fu4Pointni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#OutputFu4Point

Output value
belongs to
output

Heating Sequence Patternni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#FbSequenceHeatingPattern

Pattern of function block for Heating Sequence (FbSequenceHeating)
belongs to
Enumerated control function pattern c
Heating sequence c

Mixed Air Sequence Patternni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#FbSequenceMixedAirPattern

Pattern of function block for Mixed Air Sequence (FbSequenceMixedAir)
belongs to
Enumerated control function pattern c
Mixed air sequence c

Plate-Type Heat Exchanger Patternni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#FbPlateHeatExchangerPattern

Pattern of function block for Plate-Type Heat Exchanger (FbPlateHeatExchanger)
belongs to
Enumerated control function pattern c
Plate-Type heat exchanger c

rActualBoilerTemperatureni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rActualBoilerTemperature

Actual boiler temperature [°C]
belongs to
input

rActualPositionni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rActualPosition

Actual position of the continuous damper [%]
belongs to
input

rActualReturnTemperatureni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rActualReturnTemperature

Actual boiler return temperature [°C]
belongs to
input

rActualValueni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rActualValue

Actual value [°C]
belongs to
input

rExhaustAirTemperatureni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rExhaustAirTemperature

Actual value for exhaust air temperature [°C]
belongs to
input

rExitAirTemperatureni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rExitAirTemperature

Actual value exhaust air temperature [°C]
belongs to
input

rInputni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rInput

Input value
belongs to
input

rManualValueni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rManualValue

Set value in manual mode [%] or [°C] Value range = 0 – 100% Default setting = 22 °C
belongs to
input

rManualValueValveni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rManualValueValve

Valve position in Manual mode [%]
belongs to
input

rMaxReferenceValueni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rMaxReferenceValue

Maximum reference value for slave controller
belongs to
output

rMinBoilerTemperatureni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rMinBoilerTemperature

Minimum boiler temperature
belongs to
output

rMinExitAirni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rMinExitAir

Minimum exhaust air temperature for regulation of the plate-type heat exchanger in the incoming air duct [°C] Default setting = 6 °C
belongs to
input

rMinReferenceValueni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rMinReferenceValue

Minimum reference value for slave controller
belongs to
output

rOutputni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rOutput

Filtered output value
belongs to
output

rOutsideTemperatureni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rOutsideTemperature

Actual value outside temperature [°C]
belongs to
input

rReferenceBoilerTemperatureni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rReferenceBoilerTemperature

Specified boiler temperature [°C]
belongs to
input

rReferencePositionni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rReferencePosition

Reference position of the continuous damper [%]
belongs to
input

rReferenceValueni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rReferenceValue

Reference value [°C] Default setting = 22 °C
belongs to
input

rReferenceValueSlaveControllerni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rReferenceValueSlaveController

Reference value for slave controller [°C]
belongs to
output

rValvePositionni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rValvePosition

Specified position of valve [%]
belongs to
input

rX1ni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rX1

x-coordinate of the first value
belongs to
input

rX2ni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rX2

x-coordinate of the second value
belongs to
input

rYni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rY

Set value [%]
belongs to
input
output

rY1ni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rY1

y-coordinate of the first value
belongs to
input

rY2ni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rY2

y-coordinate of the second value
belongs to
input

rY_DamperExhaustAirni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rY_DamperExhaustAir

Set value for plate-type heat exchanger in exhaust air duct [%] Value range = 0 – 100
belongs to
output

rY_DamperSupplyAirni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rY_DamperSupplyAir

Set value for plate-type heat exchanger in incoming air duct [%] Value range = 0 – 100
belongs to
output

rY_Dehumidifyingni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rY_Dehumidifying

Set value for dehumidifier [%]
belongs to
input

rY_EnergyRecoveryni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rY_EnergyRecovery

Set value for energy recovery [%]
belongs to
input
output

rY_FreshAirni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rY_FreshAir

Set value mixed air damper [%]
belongs to
output

rY_Heatingni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rY_Heating

Valve position heating register
belongs to
output

rY_MinFreshAirni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rY_MinFreshAir

Minimum fresh air rate [%]
belongs to
input

rY_Valveni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#rY_Valve

Valve position, 3-way valve [%]. Value range = 0 – 100
belongs to
output

Sequence Controller Patternni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#FbSequenceControllerPattern

Pattern of function block for Sequence Controller (FbSequenceController)
belongs to
Enumerated control function pattern c
Sequence controller c

typSequenceControllerni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#typSequenceController

Data structure for data exchange between the individual sequences and the sequence controller
belongs to
input

typStatusBoilerni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#typStatusBoiler

Boiler status for the strategy module
belongs to
output

Valve and Pump Patternni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#FbValveAndPumpPattern

Pattern of function block for Valve and Pump (FbValveAndPump)
belongs to
Enumerated control function pattern c
Ventil und Pumpe c

wStatusni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#wStatus

Display current status 0 = OK 1 = On 2 = Off 10 = Error Pump 29 = Error Safety chain 30 = Condensation protection 31 = Chimney sweep function 32 = Overheating protection 33 = Error Valve 34 = Follow up time 35 = Manual operation 36 = In motion 39 = Reference value exceeded 40 = Startup behaviour 42 = Error Damper position 46 = Error limit switch 47 = Synchronisation
belongs to
output

wYni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#wY

Set value: Value range: 0 −32767 for damper
belongs to
output

wY_DamperExhaustAirni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#wY_DamperExhaustAir

Set value for plate-type heat exchanger in the exhaust air duct Value range = 0 – 32767
belongs to
output

wY_DamperSupplyAirni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#wY_DamperSupplyAir

Set value for plate-type heat exchanger in the incoming air duct Value range = 0 – 32767
belongs to
output

wY_EnergyRecoveryni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#wY_EnergyRecovery

Set value for energy recovery Value range = 0 – 32767
belongs to
output

wY_FreshAirni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#wY_FreshAir

Set value for mixed air damper Value range = 0 – 32767
belongs to
output

wY_Heatingni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#wY_Heating

Valve position heating register Value range = 0 – 32767
belongs to
output

wY_Valveni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#wY_Valve

Valve position, 3-way valve. Value range = 0 – 32767
belongs to
output

xActiveni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xActive

Active indicator for sequence
belongs to
output

xAdmixingPumpni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xAdmixingPump

Switching signal for the admixing pump
belongs to
output

xAlarmni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xAlarm

Output signal error
belongs to
output

xAutoni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xAuto

Automatic mode
belongs to
input

xBoilerPumpni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xBoilerPump

Boiler circuit pump
belongs to
output

xChimneySweepni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xChimneySweep

Chimney sweep function active
belongs to
output

xChimneySweepFunctionni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xChimneySweepFunction

Activate chimney sweep function
belongs to
input

xCloseni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xClose

Engine coil CLOSED
belongs to
output

xCondensationProtectionni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xCondensationProtection

Condensation protection
belongs to
output

xDifferentialPressureMonitorni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xDifferentialPressureMonitor

Differential pressure sensor plate-type heat exchanger Default setting = TRUE
belongs to
input

xEnableni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xEnable

Enable controller Default setting = TRUE
belongs to
input

xEnablePumpni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xEnablePump

Enable pump and valve control
belongs to
input

xEnableSystemni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xEnableSystem

Enable FbStartStop Default setting = TRUE
belongs to
input

xErrorni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xError

Some fault
belongs to
output

xErrorAdmixingPumpni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xErrorAdmixingPump

Admixing pump error
belongs to
output

xErrorBoilerPumpni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xErrorBoilerPump

Boiler circuit pump error
belongs to
output

xErrorPumpni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xErrorPump

Error message pump
belongs to
output

xErrorSequenceni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xErrorSequence

Error check-back signal from device
belongs to
input

xErrorStartUpni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xErrorStartUp

Start-up system fault
belongs to
output

xFeedbackManualOperationni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xFeedbackManualOperation

External check-back signal, Manual mode
belongs to
input

xFollowUpTimeni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xFollowUpTime

Pump is in the follo-up phase
belongs to
output

xFrostAlarmAirni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xFrostAlarmAir

Frost alarm from FbAntifreezeAir
belongs to
input

xFrostAlarmWaterni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xFrostAlarmWater

Frost alarm from FbAntifreezeWater
belongs to
input

xFullLoadni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xFullLoad

Boiler is to run at full load
belongs to
input

xInitni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xInit

A positive flank starts the reference run
belongs to
input

xLevel1ni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xLevel1

Boiler Level 1
belongs to
output

xLevel2ni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xLevel2

Boiler Level 2
belongs to
output

xLimitSwitchni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xLimitSwitch

Limit switch (opend, closed)
belongs to
input

xLimitSwitchValveni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xLimitSwitchValve

Limit switch, 2-way valve. Default setting = TRUE
belongs to
input

xManualni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xManual

Manual mode
belongs to
input

xManualOnAdmixingPumpni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xManualOnAdmixingPump

Switch on admixing pump manually
belongs to
input

xManualOnBoilerPumpni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xManualOnBoilerPump

Switch on boiler circuit pump manually
belongs to
input

xManualOperationni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xManualOperation

Enable manual operation
belongs to
input

xManualSwitchPumpni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xManualSwitchPump

Switch on pump manually
belongs to
input

xMaximalThermostatni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xMaximalThermostat

Maximum thermostat for heating circuit Default setting = TRUE
belongs to
input

xMinFreshAirni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xMinFreshAir

Override mixed air damper using the minimum fresh air rate
belongs to
input

xMotorProtectionni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xMotorProtection

Motor protection switch pump Default setting = TRUE
belongs to
input

xMotorProtectionAdmixingPumpni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xMotorProtectionAdmixingPump

Motor protection switch, Admixing pump. Default setting = TRUE
belongs to
input

xMotorProtectionPumpni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xMotorProtectionPump

Motor protection switch, Boiler circuit pump. Default setting = TRUE
belongs to
input

xNightVentilationni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xNightVentilation

Opening damper during night ventilation
belongs to
input

xOpenni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xOpen

Engine coil OPEN
belongs to
output

xPumpni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xPump

Switching signal for the pump
belongs to
output

xQuitni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xQuit

Error message acknowledgement
belongs to
input

xRepairSwitchni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xRepairSwitch

Repair switch pump Default setting = TRUE
belongs to
input

xRepairSwitchAdmixingPumpni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xRepairSwitchAdmixingPump

Repair switch, Admixing pump. Default setting = TRUE
belongs to
input

xRepairSwitchPumpni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xRepairSwitchPump

Repair switch, Boiler circuit pump. Default setting = TRUE
belongs to
input

xSafetyChainni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xSafetyChain

Check-back signal from boiler safety chain. Default setting = TRUE
belongs to
input

xSpeedLevel1ni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xSpeedLevel1

Request fan level 1
belongs to
output

xSpeedLevel2ni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xSpeedLevel2

Request fan level 2
belongs to
output

xSwitchOnBoilerni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xSwitchOnBoiler

Switch-on signal in Automatic mode (e.g., from boiler strategy)
belongs to
input

xValveni back to ToC or Named Individual ToC

IRI: https://w3id.org/baf#xValve

Switching signal 2-way valve
belongs to
output

Legend back to ToC

c: Classes
ni: Named Individuals

References back to ToC

Add your references here. It is recommended to have them as a list.